996 Turbo diagnostic manual — Turbo applicability only / PAGE 377
80-11Fault code 25 · Supply voltage (5 V) - too high/ too low
Read extracted page text
OCR can contain errors. Check the original page image for exact wording, warnings and specifications.
911 Turbo (996) Air conditioning H01, H02 80
80-11Fault code 25
Supply voltage (5 V) - too high/ too low
Diagnostic conditions
• Ignition on
Note!
No control module fault stored
Possible cause of fault
♦Short circuit to voltage/ground or open circuit in the wiring
between the air-conditioning system regulator and the four flap
motors.
♦Air-conditioning system regulator faulty
Affected terminals
Plug B, terminals 9 and 20
Diagnosis/troubleshooting
Work instruction Display OK If not OK
1 Check 5 V supply lead for ♦Switch off ignition 0 V Repair wiring har-
short to B+ ⇒ Step 2 ness→ End ♦Remove plug B from the air-con-
ditioning system regulator
♦Switch on ignition
♦Measure voltage at plug B of the
air-conditioning system regula-
tor between pin 20 and ground
2 Check 5 V - supply line ♦Switch off ignition approx. 5 V If more than 5.5 V is
⇒ Step 4 indicated: ♦Replace plug B on the air-condi-
⇒ Step 8 tioning system regulator
If 0 V is indicated:
♦Remove connector for tempera- ⇒ Step 3
ture mixing valve
♦Switch on ignition
♦Measure voltage at plug of the
flap motor between pin 3 and
ground
8001 Fault code 25 80-11 page 1
Printed in Germany – 15, 2001 25xxxh02
This is a source reference. Confirm exact model applicability in the original material.